SIS |
|
Cross-Linked polyethylene insulated tinned or bare, stranded copper conductor. For use in the wiring of switchboards, panel boards, and distribution boards. Rated 90°C 600V in dry locations. |
Product Summary |
|
UL/CSA Listed Type SIS XLPE Insulated UL 44 Thermoset-Insulated Wire and Cables 90°C, 600V (UL) AWM 125°C, 600V RoHS Available |

|
INDUSTRIAL WIRE AND CABLE CORP |
|
Premier manufacturer of high quality copper wire and cable products. |
|
IWC P/N |
AWG Stranding |
COND. DIA. (inches) |
FIN. O.D. (inches) |
APPROX. FIN. WT. (lbs./M’) |
|
SIS1441 |
14 (41/30) BC |
.075 |
.138 |
18 |
|
SIS1265 |
12 (65/30) BC |
.095 |
.158 |
27 |
|
SIS10105 |
10 (105/30) BC |
.120 |
.183 |
40 |
|
SIS08133 |
8 (133/29) BC |
.166 |
.260 |
67 |
|
SIS04133 |
4 (7x19/25) BC |
.257 |
.381 |
162 |
|
SIS1Ø259 |
1/0 (7x37/24) BC |
.422 |
.592 |
408 |
|
SIS1Ø1045 |
1/0 (19x55/30) BC |
.406 |
.576 |
424 |
|
SIS4Ø259 |
4/0 (7x37/21) BC |
.606 |
.786 |
760 |
|
SIS4Ø2107 |
4/0 (7x7x43/30) BC |
.625 |
.800 |
750 |
|
Optional VW-1 rated Linear stripes from 10-40 % coverage available |
||||
|
|
|||
|
PROPERTIES |
TEST METHOD |
UNITS |
VALUE |
|
Specific Gravity |
ASTM D-792 |
|
1.01 |
|
Tensile Strength |
ASTM D-638 |
psi |
2800 |
|
Elongation |
|
% |
400 |
|
Oven Ageing 14 days @ 121°C Retention of tensile Retention of elongation |
ASTM D-1870
|
% % |
95 90 |
|
Deformation |
CSA 22.2 No. 3 |
% |
10 |
|
Gel |
ASTM D-2765 |
% |
68 |
|
Horizontal Flame |
UL 1581 CSA FT-2 |
|
Pass Pass |
|
Dielectric Constant @1 MHz |
ASTM D-150-95 |
|
2.31 |
|
Dissipation Factor @ 1 MHz |
ASTM D-150-95 |
|
0.0012 |
|
L.O.I |
ASTM D-2863 |
% |
23 |